FEATURES

  • Analysis for 3 phase multi-power system, 1P/2W,
    1P/3W, 3P/3W, 3P/4W.
  • Voltage & Current are the True RMS value.
  • True Power ( KW、MW、GW ) measurement.
  • Apparent Power ( KVA、MVA、GVA ) measurement.
  • Reactive Power ( KVAR MVAR、GVAR) measurement.
  • Watt-Hour ( WH、SH、QH、PFH ).
  • Power Factor( PF )、Phase Angle( Φ ).
  • Voltage measurement range : 10 to 600 ACV
  • Current measurement range: 0.2A to 1200 ACA.
  • Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
  • ACV input impedance is 10 Mega ohms.
  • Safety Standard : IEC 1010, CAT III 600V
  • Built-in clock and Calendar, real time data record with
    SD memory card , sampling time set from 2 to 7200
    seconds. Just slot in the SD card into the computer, it
    can down load the all the measured value with the
    time information ( year/month/data/
    hour/mimute/second ) to the Excel directly, then user
    can make the further data analysis by themselves.
  • Complete set with 4 PCs Test Leads, 4 PCs Alligator
    clips, 3 PCs Clamp Probe, AC to DC 9V adapter,
    2 G SD memory card and Carrying bag.
  • Computer data output, can cooperate with USB Cable
    /USB-01 RS232 cable/UPCB-02 and Data Acquisition
    software, SW-U811-WIN.

2 in stock

SKU: DW-6092 Category: Tag:

Product Description

SPECIFICATIONS
Circuit Custom one-chip of microprocessor LSI
circuit.
Display * LCD Size :
81.4 X 61 mm ( 3.2 X 2.4 inch )
* Dot Matrix LCD (320 X 240 pixels )
with back light.
Measurement * ACV
* ACA
* AC WATT ( True Power )
AC WATT( Apparent Power )
AC WATT( Reactive Power )
* Power factor
* Phase angle
* Frequency
Wire
connections
1P/2W, 1P/3W, 3P/3W, 3P/4W.
Voltage ranges 10 ACV to 600 ACV, auto range.
Current ranges 0.2 ACA to 1200 ACA,
auto range/manual range.
Safety
standard
IEC1010 CAT III 600 V.
ACV input
impedance
10 Mega ohms.
Range select ACV – Auto range.
ACA – Auto range & manual range.
Clamp
frequency
response
40 Hz to 1 KHz.
Spec. tested
frequency
45 to 65 Hz.
Over load
protection
ACV -720 ACV rms
ACA -1300 ACA with clamp probe
CP-1200
Over Indicator Show ” OL “.
Under Indicator Show ” UR “.
Data Hold/
Data Record
 Freeze the display reading./

SD Card Record.

Sampling Time Approx. 1 second.
Power ON/OFF Manual OFF by push button.
Real time
data logger
* Real time data logger, saved the data
into SD memory card and down load
the all the measured value with the
time information ( year/month/data/
hour/mimute/second ) down load
to the Excel* Integration time for data logger :
2 seconds to 7200 seconds, the during
of setting step are 2 seconds.
Data Output
USB/RS232
* Computer
interface
RS232 computer serial interface :
* Connect the optional USB cable
USB-01 will get the USB plug.
* Connect the optional RS232 cable
UPCB-02 will get the RS232
plug.
Operating
Temperature
0 to 50℃ ( 0 to 122℉ ).
Operating
Humidity
Less than 80% R.H..
Power Supply * DC 1.5V, AA ( UM-3 ) Battery X 8 PCs
(Alkaline or heavy duty battery).
* AC to DC 9V power adapter.
Power
Consumption
* Meter : 300 DCmA.
* Clamp : 20 DCmA.
Clamp max.
conductor
Size
86 mm ( 3.4 inch ) Dia.
Weight * Meter: 1049g ( includes batteries )
* Clamp : 522g
Dimension Meter : 225 X 125 X 64 mm
( 8.86 X 4.92 X 2.52 inch )
Clamp : 210 X 64 X 33mm
( 8.3 X 2.5 X 1.3 inch )
Clamp Jaw : 50 mm (2.0 inch)- outside